This summarizes how to get warning info, as well as, contents of and conditions for warning transmissions.
Get Warning Report Mails
In the settings screen of the server (T&D WebStorage Service / T&D Data Server), enter recipient e-mail addresses to which you want to have warning reports sent.
View Warnings in a Browser Window
View on Smart Device via Push Notification and/or in the App’s Warning List
When the Auto-Upload Destination is T&D WebStorage Service, you can receive alerts via push notification by installing T&D Thermo on your smart device and making the necessary settings. (For details, refer to the Help of T&D Thermo.)
Check the [ALM] Indicator on the Device Screen (TR7A only)
The [ALM] icon will blink on the LCD to indicate the occurrence of a warning.
Check the Warning Log
T&D WebStorage Service / T&D Data Server sends the following email when it receives a warning from a device.
Sender | The sender is an e-mail address from within the webstorage-service.com domain. Please set your mail software (or mail server, if necessary) to receive e-mails from the above domain. |
---|---|
Recipient | If you are using T&D WebStorage Service, you can add recipients from the Account Management screen after logging in from a browser. If you are using T&D Data Server, you can set up and add recipients from the Warning Mail Settings screen in the Manager screen. |
Time Stamp | The time when a warning condition was detected and the judgment countdown started. |
Transmission Date/ Time and Device Info |
The date and time when the device created the warning data and the device name. |
Warning Status and Content | Varies depending on the warning condition as shown below. |
EXAMPLES
Upper Limit / Lower Limit Warning Activated | |
Upper Limit / Lower Limit Warning Recovered | |
Sensor Error |
|
Sensor Error Recovered | |
Sensor Error Recovered Upper Limit / Lower Limit Warning (TR7A) |
|
Low Battery Warning | |
Low Battery Warning Recovered | |
Warning Lifted (TR7A) |
Transmission takes place only when Auto-upload is enabled, the target warning is set to ON and either a warning or a recovery occurs.
Refer to the following for warning and recovery conditions by model, mode, and type of warning.
For TR7A and TR-7nw/wb/wf in Normal Mode
Types of Warnings | Conditions for Issuing Warnings | Conditions for Recovery |
---|---|---|
Upper Limit/Lower Limit Exceeded (for each channel) |
When a measurement exceeds the set threshold value (above the upper limit or below the lower limit) for longer than the set Warning Judgment Time.
|
When the measured value returns to within the specified range and/or when the ALM display*1 is cleared. |
Sensor Error (for each channel) |
When Sensor Warning is enabled and a sensor problem (e.g., sensor not connected, damaged, and poor connection) continues for the set Warning Judgment Time. | When the sensor returns to normal and measurement is possible. |
Battery Level*2 | When Battery Warning is enabled and a low battery condition is detected. (Batteries need to be replaced.) |
When the battery level becomes OK after replacement of batteries.*3 |
*1: This function is only available for TR7A. To clear the ALM display, perform any of the following: |
For TR71A/75A in Vaccine Mode
Types of Warnings | Conditions for Issuing Warnings | Conditions for Recovery |
---|---|---|
Upper Limit/Lower Limit Exceeded (for each channel) |
When a recorded value exceeds the set threshold value (above the upper limit or below the lower limit) at the timing of recording based on the recording interval.
|
When the ALM display is cleared.*1 |
Sensor Error (for each channel) |
When Sensor Warning is enabled and a sensor problem (e.g., sensor not connected, damaged, and poor connection) is detected at the recording interval. | When the sensor returns to normal and measurement is possible. |
Battery Level | When Battery Warning is enabled and a low battery condition is detected. (Batteries need to be replaced.) |
When the battery level becomes OK after replacement of batteries. |
*1:To clear the ALM display, perform any of the following |
In addition to notification of various types of warnings and recovery from warning conditions, TR7A will also notify the user when warning has been lifted.
(Compatible Devices: TR71A/72A(-S) firmware Ver. 1.19 or later, TR75A firmware Ver. 1.05 or later)
Warning will be lifted when one of the following takes place while the device is in a warning state:
Q&A about TR7 Series Devices - [Q12: How can I check my firmware version and update it when necessary? ]
When Warning Data Transmission from Data Logger to Server Fails:
E.g., Wireless LAN communication failure, data logger battery too low, T&D Data Server stopped during backup, etc.
TR7 series will send a warning at the next auto-uploading cycle.
When Warning Email Transmission from Server Fails:
E.g., Communication with the mail server is temporarily unavailable.
T&D WebStorage Service will try resending periodically within a day or so.
T&D Data Server will resend 10 minutes after a transmission error (up to 2 times).
Upon Warning Transmission Failure:
Because the number of warnings that can be stored is limited, older warning notifications may not occur when transmission from a device to a server fails.
The TR7A stores the latest 5 warning events (2 for battery warning).
The TR-7nw/wb/wf stores only the latest 1 event.
Example: If two events, Upper Limit Warning and Recovery occur, TR7A will notify of both events, but TR-7nw/wb/wf will notify only Recovery (Back to Normal) event.